Notifications
You must be signed in to change notification settings - Fork 6
Expand file tree
/
Copy pathhuawei.lua
More file actions
379 lines (338 loc) · 13.9 KB
/
Copy pathhuawei.lua
File metadata and controls
379 lines (338 loc) · 13.9 KB
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
-- Huawei SUN2000 Hybrid Inverter Driver
-- Emits: PV, Battery, Meter
-- Protocol: Modbus TCP, ALL HOLDING registers, Big-Endian word order
--
-- Ported from sourceful-hugin/device-support/drivers/lua/huawei.lua
-- for FTW Lua host v2.1.
--
-- Reference: Huawei SUN2000 Modbus Interface Definition
-- (inverter + LUNA2000 battery module via SDongle / embedded Modbus TCP).
--
-- Sign convention (site convention — positive W = INTO the site):
-- pv.w: always negative (generation)
-- battery.w: positive = charging, negative = discharging
-- meter.w: positive = import from grid, negative = export
--
-- Huawei's meter register reports power with the OPPOSITE sign from our
-- convention (positive = export on Huawei), so meter power + per-phase
-- power + per-phase current are all negated at the boundary.
DRIVER = {
host_api_min = 1,
host_api_max = 1,
id = "huawei-sun2000",
name = "Huawei SUN2000 Hybrid Inverter",
manufacturer = "Huawei",
version = "1.0.0",
protocols = { "modbus" },
capabilities = { "meter", "pv", "battery" },
description = "Huawei SUN2000 hybrid inverters with LUNA2000 battery via Modbus TCP.",
homepage = "https://solar.huawei.com",
authors = { "FTW contributors" },
tested_models = { "SUN2000L1", "SUN2000-LUNA2000" },
verification_status = "experimental",
verification_notes = "Ported from a reference implementation. Not yet verified against live hardware on a FTW site.",
connection_defaults = {
port = 502,
unit_id = 1,
},
}
PROTOCOL = "modbus"
local sn_read = false
----------------------------------------------------------------------------
-- Helpers
----------------------------------------------------------------------------
-- Write a U32 value split across two consecutive holding registers (BE).
-- Used for forcible charge/discharge power targets (watts).
local function write_u32(addr, val)
val = math.floor(math.abs(val))
local hi = math.floor(val / 65536)
local lo = val % 65536
host.modbus_write_multi(addr, { hi, lo })
end
-- Decode a 10-register ASCII string (20 bytes, big-endian packing).
-- Skips bytes outside printable ASCII.
local function decode_ascii(regs, n)
local s = ""
for i = 1, n do
local hi = math.floor(regs[i] / 256)
local lo = regs[i] % 256
if hi > 32 and hi < 127 then s = s .. string.char(hi) end
if lo > 32 and lo < 127 then s = s .. string.char(lo) end
end
return s
end
----------------------------------------------------------------------------
-- Initialization
----------------------------------------------------------------------------
function driver_init(config)
host.set_make("Huawei")
host.log("info", "Huawei SUN2000: driver_init")
end
----------------------------------------------------------------------------
-- Telemetry polling
----------------------------------------------------------------------------
function driver_poll()
-- Read serial number once (register 30015, 10 registers, ASCII).
if not sn_read then
local ok, sn_regs = pcall(host.modbus_read, 30015, 10, "holding")
if ok and sn_regs then
local sn = decode_ascii(sn_regs, 10)
if string.len(sn) > 0 then
host.set_sn(sn)
sn_read = true
host.log("info", "Huawei SUN2000: SN=" .. sn)
end
end
end
-- ---- PV ----
-- PV1 V/A: 32016-32017, I16 × 0.1 V, I16 × 0.01 A
local ok_pv1, pv1_regs = pcall(host.modbus_read, 32016, 2, "holding")
local pv1_v, pv1_a = 0, 0
if ok_pv1 and pv1_regs then
pv1_v = host.decode_i16(pv1_regs[1]) * 0.1
pv1_a = host.decode_i16(pv1_regs[2]) * 0.01
end
-- PV2 V/A: 32018-32019, I16 × 0.1 V, I16 × 0.01 A
local ok_pv2, pv2_regs = pcall(host.modbus_read, 32018, 2, "holding")
local pv2_v, pv2_a = 0, 0
if ok_pv2 and pv2_regs then
pv2_v = host.decode_i16(pv2_regs[1]) * 0.1
pv2_a = host.decode_i16(pv2_regs[2]) * 0.01
end
-- Input power (PV total): 32064-32065, I32 BE × 0.001 kW → × 1000 for W
local ok_pvw, pvw_regs = pcall(host.modbus_read, 32064, 2, "holding")
local pv_w = 0
if ok_pvw and pvw_regs then
pv_w = host.decode_i32_be(pvw_regs[1], pvw_regs[2]) * 0.001 * 1000
end
-- Inverter temperature: 32087, I16 × 0.1 °C
local ok_itemp, itemp_regs = pcall(host.modbus_read, 32087, 1, "holding")
local inv_temp = 0
if ok_itemp and itemp_regs then
inv_temp = host.decode_i16(itemp_regs[1]) * 0.1
end
-- PV lifetime yield: 32106-32107, U32 BE × 0.01 kWh → × 1000 for Wh
local ok_yield, yield_regs = pcall(host.modbus_read, 32106, 2, "holding")
local pv_gen_wh = 0
if ok_yield and yield_regs then
pv_gen_wh = host.decode_u32_be(yield_regs[1], yield_regs[2]) * 0.01 * 1000
end
-- ---- Battery ----
-- Battery power: 37001-37002, I32 BE, watts
-- Huawei sign: positive = charging, negative = discharging (matches site convention).
local ok_bw, bw_regs = pcall(host.modbus_read, 37001, 2, "holding")
local bat_w = 0
if ok_bw and bw_regs then
bat_w = host.decode_i32_be(bw_regs[1], bw_regs[2])
end
-- Battery bus voltage: 37003, U16 × 0.1 V
local ok_bv, bv_regs = pcall(host.modbus_read, 37003, 1, "holding")
local bat_v = 0
if ok_bv and bv_regs then
bat_v = bv_regs[1] * 0.1
end
-- Battery SoC: 37004, U16 × 0.1 percent (convert to 0-1 fraction).
local ok_bsoc, bsoc_regs = pcall(host.modbus_read, 37004, 1, "holding")
local bat_soc = 0
if ok_bsoc and bsoc_regs then
bat_soc = bsoc_regs[1] * 0.1 / 100
end
-- Battery current: 37021, I16 × 0.1 A
local ok_ba, ba_regs = pcall(host.modbus_read, 37021, 1, "holding")
local bat_a = 0
if ok_ba and ba_regs then
bat_a = host.decode_i16(ba_regs[1]) * 0.1
end
-- Battery temperature: 37022, I16 × 0.1 °C
local ok_btemp, btemp_regs = pcall(host.modbus_read, 37022, 1, "holding")
local bat_temp = 0
if ok_btemp and btemp_regs then
bat_temp = host.decode_i16(btemp_regs[1]) * 0.1
end
-- Battery charge/discharge lifetime energy: 37066-37069, U32 BE × 0.01 kWh pairs.
local ok_benergy, benergy_regs = pcall(host.modbus_read, 37066, 4, "holding")
local bat_charge_wh, bat_discharge_wh = 0, 0
if ok_benergy and benergy_regs then
bat_charge_wh = host.decode_u32_be(benergy_regs[1], benergy_regs[2]) * 0.01 * 1000
bat_discharge_wh = host.decode_u32_be(benergy_regs[3], benergy_regs[4]) * 0.01 * 1000
end
-- ---- Meter ----
-- Per-phase voltage: 37101-37106, I32 BE × 0.1 pairs (L1 V, L2 V, L3 V)
local ok_lv, lv_regs = pcall(host.modbus_read, 37101, 6, "holding")
local l1_v, l2_v, l3_v = 0, 0, 0
if ok_lv and lv_regs then
l1_v = host.decode_i32_be(lv_regs[1], lv_regs[2]) * 0.1
l2_v = host.decode_i32_be(lv_regs[3], lv_regs[4]) * 0.1
l3_v = host.decode_i32_be(lv_regs[5], lv_regs[6]) * 0.1
end
-- Per-phase current: 37107-37112, I32 BE × 0.01 pairs (L1 A, L2 A, L3 A)
local ok_la, la_regs = pcall(host.modbus_read, 37107, 6, "holding")
local l1_a, l2_a, l3_a = 0, 0, 0
if ok_la and la_regs then
l1_a = host.decode_i32_be(la_regs[1], la_regs[2]) * 0.01
l2_a = host.decode_i32_be(la_regs[3], la_regs[4]) * 0.01
l3_a = host.decode_i32_be(la_regs[5], la_regs[6]) * 0.01
end
-- Meter total power: 37113-37114, I32 BE, watts.
-- Huawei sign: positive = export, negative = import. Negate for site convention.
-- If this read fails, skip ALL emits so the watchdog catches staleness —
-- emitting PV/battery while meter is down would keep the driver "healthy"
-- but give the control loop a stale grid reading.
local ok_mw, mw_regs = pcall(host.modbus_read, 37113, 2, "holding")
if not ok_mw or not mw_regs then
host.log("warn", "Huawei: meter power read failed, skipping all emits")
return 5000
end
local meter_w = host.decode_i32_be(mw_regs[1], mw_regs[2])
-- Grid frequency: 37118, I16 × 0.01 Hz
local ok_hz, hz_regs = pcall(host.modbus_read, 37118, 1, "holding")
local hz = 0
if ok_hz and hz_regs then
hz = host.decode_i16(hz_regs[1]) * 0.01
end
-- Export/Import lifetime energy: 37119-37122, I32 BE × 0.01 kWh pairs
local ok_energy, energy_regs = pcall(host.modbus_read, 37119, 4, "holding")
local export_wh, import_wh = 0, 0
if ok_energy and energy_regs then
export_wh = host.decode_i32_be(energy_regs[1], energy_regs[2]) * 0.01 * 1000
import_wh = host.decode_i32_be(energy_regs[3], energy_regs[4]) * 0.01 * 1000
end
-- Per-phase power: 37132-37137, I32 BE pairs, watts (Huawei sign).
local ok_lpw, lpw_regs = pcall(host.modbus_read, 37132, 6, "holding")
local l1_w, l2_w, l3_w = 0, 0, 0
if ok_lpw and lpw_regs then
l1_w = host.decode_i32_be(lpw_regs[1], lpw_regs[2])
l2_w = host.decode_i32_be(lpw_regs[3], lpw_regs[4])
l3_w = host.decode_i32_be(lpw_regs[5], lpw_regs[6])
end
-- ---- All reads succeeded — emit everything ----
-- PV telemetry (site convention: generation is negative).
host.emit("pv", {
w = -pv_w,
mppt1_v = pv1_v,
mppt1_a = pv1_a,
mppt2_v = pv2_v,
mppt2_a = pv2_a,
lifetime_wh = pv_gen_wh,
temp_c = inv_temp,
})
host.emit_metric("pv_mppt1_v", pv1_v)
host.emit_metric("pv_mppt1_a", pv1_a)
host.emit_metric("pv_mppt2_v", pv2_v)
host.emit_metric("pv_mppt2_a", pv2_a)
host.emit_metric("inverter_temp_c", inv_temp)
-- Battery telemetry.
host.emit("battery", {
w = bat_w,
v = bat_v,
a = bat_a,
soc = bat_soc,
temp_c = bat_temp,
charge_wh = bat_charge_wh,
discharge_wh = bat_discharge_wh,
})
host.emit_metric("battery_dc_v", bat_v)
host.emit_metric("battery_dc_a", bat_a)
host.emit_metric("battery_temp_c", bat_temp)
-- Negate meter power + per-phase power + per-phase current to site convention
-- (positive = import from grid).
host.emit("meter", {
w = -meter_w,
l1_w = -l1_w,
l2_w = -l2_w,
l3_w = -l3_w,
l1_v = l1_v,
l2_v = l2_v,
l3_v = l3_v,
l1_a = -l1_a,
l2_a = -l2_a,
l3_a = -l3_a,
hz = hz,
import_wh = import_wh,
export_wh = export_wh,
})
host.emit_metric("meter_l1_w", -l1_w)
host.emit_metric("meter_l2_w", -l2_w)
host.emit_metric("meter_l3_w", -l3_w)
host.emit_metric("meter_l1_v", l1_v)
host.emit_metric("meter_l2_v", l2_v)
host.emit_metric("meter_l3_v", l3_v)
host.emit_metric("meter_l1_a", -l1_a)
host.emit_metric("meter_l2_a", -l2_a)
host.emit_metric("meter_l3_a", -l3_a)
host.emit_metric("grid_hz", hz)
return 5000
end
----------------------------------------------------------------------------
-- Battery control
----------------------------------------------------------------------------
-- Battery control command handler.
-- Site convention: positive power_w = charge, negative = discharge, 0 = idle.
-- Huawei forcible-mode registers (all holding):
-- 47086: working mode (2 = maximise self-consumption)
-- 47100: forcible charge/discharge command (0=stop, 1=charge, 2=discharge)
-- 47083: forcible charge/discharge period (minutes; must be re-sent each command)
-- 47246: forcible-mode kind (0 = duration-based)
-- 47247-47248: forcible charge power (U32, watts)
-- 47249-47250: forcible discharge power (U32, watts)
function driver_command(action, power_w, cmd)
if action == "init" then
-- Duration-based forcible mode, 24 h cap so we don't need to re-arm often.
host.modbus_write(47246, 0)
host.modbus_write(47083, 1440)
return true
elseif action == "battery" then
return set_battery_power(power_w)
elseif action == "curtail" then
-- Force charge to absorb excess PV.
write_u32(47247, math.abs(power_w))
host.modbus_write(47083, 1440)
host.modbus_write(47100, 1)
host.log("debug", "Huawei: curtail (force charge) " .. tostring(math.abs(power_w)) .. "W")
return true
elseif action == "curtail_disable" then
host.modbus_write(47100, 0)
host.log("debug", "Huawei: curtail_disable")
return true
elseif action == "deinit" then
return set_self_consumption()
end
return false
end
-- Drive the battery to a specific setpoint.
-- power_w > 0: forcible charge at power_w W
-- power_w < 0: forcible discharge at |power_w| W
-- power_w = 0: stop forcible mode (device resumes self-consumption).
function set_battery_power(power_w)
if power_w > 0 then
write_u32(47247, power_w)
host.modbus_write(47083, 1440)
host.modbus_write(47100, 1)
host.log("debug", "Huawei: force charge " .. tostring(power_w) .. "W")
elseif power_w < 0 then
write_u32(47249, math.abs(power_w))
host.modbus_write(47083, 1440)
host.modbus_write(47100, 2)
host.log("debug", "Huawei: force discharge " .. tostring(math.abs(power_w)) .. "W")
else
host.modbus_write(47100, 0)
host.log("debug", "Huawei: stop forcible mode")
end
return true
end
-- Revert to autonomous self-consumption (safe default).
function set_self_consumption()
host.modbus_write(47100, 0) -- stop forcible mode
host.modbus_write(47086, 2) -- maximise self-consumption
host.log("debug", "Huawei: self-consumption mode")
return true
end
-- Watchdog fallback: always revert to autonomous self-consumption.
function driver_default_mode()
host.log("info", "Huawei: watchdog -> reverting to self-consumption")
set_self_consumption()
end
function driver_cleanup()
set_self_consumption()
sn_read = false
end